Ventilating Schedule

VENTILATING SCHEDULE

FACTORY
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Painting Room 20
Dynamo Room & Substation 20
Condenser Room 15
Office 6
HOTEL
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Dance Hall 8
Dining Hall 8 8
Kitchen 15
Hallway 5
Toilet 5
Lavatory 10
Boiler Room 20
Laundry 15
HOSPITAL
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Waiting Room 10
Clinic 6
Ward 6
Bathroom 5
Office 6
Restaurant 8
Kitchen 15
Gallery 5
Toilet 10
Toiler Room 10
Laundry 15
OFFICE
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Building Office 6
Waiting Room 10
Conference Room 12
Display Room 10
Toilet 10
OPERATING ROOM
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Operating Room 15
Disinfecting Room 12
Room for patients receiving medical treatement for diseases of respiratory organs. 10
PHOTO STUDIO
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Dark Room 10
PUBLIC TOILET
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Toilet 20
Toilet Room 20
RESTAURANT & SNACK BAR
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Restaurant 6
Kitchen 20
ROOMS WHERE POISONOUS OR INFLAMMABLE GAS IS PRODUCED
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
- 20
SCHOOL
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Laboratory 5
Cooking Room 15
Auditorium 6
Gymnasium 8
Toilet 12
Library 6
Classroom 6
THEATER
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Auditorium 6
Hallway 6
Smoking Room 12
Toilet 10
Projection Booth 20
Workroom 6
Telephone Switchboard Room 6
VESSEL
A (TYPE OF ROOM) B (NECESSARY FREQUENCY OF VENTILATION PER HOUR)
Reading Room 6